UV contrast that locates all leak points in AC-R systems!
REVELA FUGAS K11® is a high-performance fluorescent UV contrast developed for fast and accurate detection of refrigerant and lubricating oil leaks in refrigeration and air conditioning (HVAC-R) systems. Its advanced formulation allows immediate location of microleaks by fluorescence under UV or violet light, without compromising the efficiency or components of the system.
It is a product with “universal” characteristics as it is compatible with all types of refrigerant fluids (HFC, HCFC, CFC, HFO), accepted lubricants (minerales, POE, PAG, AB (alkyl-benzene) and in all types of refrigeration equipment and air conditioning.
REVELA FUGAS K11® is ideal for preventive and corrective maintenance in systems of any size or application.
CERTIFIED PRODUCT!



TECHNICAL CHARACTERISTICS
- Intense fluorescence under ultraviolet (UV) and violet light
- Compatible with all types of refrigerants (HFC, HCFC, CFC, HFO)
- Non-corrosive – safe for metals, rubbers and plastics
- High miscibility with compressor lubricating oils
- Stable over a wide range of operating temperatures
- Free from aggressive solvents and non-flammable
- Does not contain polymers
IDEAL FOR
Automotive air conditioning (passenger and cargo)
Residential and commercial air conditioning (HVAC) systems
Industrial and commercial refrigeration
Cold rooms, chillers and VRF systems
Equipment with hermetic and semi-hermetic compressors
COMPETITIVE ADVANTAGES
- Agility in diagnosing leaks that are invisible to the naked eye
- Reduced costs due to gas loss and technical rework
- Safe for the operator and the environment
- It remains active until the lubricating oil is changed.
- Leaves no harmful residue in the system after inspection
- Does not contain polymers
METHODS OF
DISTRIBUTION AND APPLICATION


Connector CO K11 is sold separately.
SYRINGE Format
- Packaging: 10 ml syringe
- Performance: Treats up to 3 liters of lubricating oil
- For pressureless or vacuum systems
- Multiple syringes can be used in systems with more than 3 liters of oil
- Applied to the low valve, with the aid of the SYRINGE X F1/4 SAE CONNECTOR WITH NON-RETURN VALVE (CO K11), following the instructions below.

Connector CO K11 is sold separately.
How to Apply
1º) Connect the SYRINGE CONNECTOR to the system’s low service valve (it can be loaded, empty or under vacuum);
2º) Screw the SYRINGE onto the SYRINGE CONNECTOR (CO K11);
3º) Slowly apply the 10ml SYRINGE. For charged systems, apply with the equipment turned on to reduce pressure;
4º) Inspect with UV or VIOLET FLASHLIGHT in a darkened room;
5º) Identify leak points by visible fluorescence at the fault site;
6º) Complete the operation by disconnecting the SYRINGE / CONNECTOR. For vacuum systems, continue with the vacuum and fluid loading operation as defined by the system manufacturer.
NOTE: Medicinal type SYRINGE, luer-lock type connection defined by ISO 594 standard.